- Giá: Liên hệ
- Lượt xem: 8205
- 040881SET Code: RM 3000IS EX smoke detector, II 1G Ex ia IIC, principle of photo-electric detection of scattered light, with base, LE
-
- Thông tin sản phẩm
- Bình luận
RM 3000IS EX smoke detector
WM 3000IS EX heat detector
For use in hazardous areas
- Approved for fire protection
- Tested and certified in compliance with EN 94/9/EG (ATEX 100)
- The RM 3000IS EX smoke detector is a stray light detector with integrated thermal sensor
- The RM 3000IS EX smoke detectors and WM 3000IS EX heat detectors are intrinsically safe
- In hazardous areas they may only be used in combination with a shunt safety barrier
- Important: They must be replaced after a maximum of 8 years of operational life to ensure the correct functioning of the hold-open system
- In Germany, the DIN 14677 regulates the replacement obligation of fire detectors in hold-open systems
Product information
| Voltage | 14 to 28 VDC |
| Protection | IP 23 |
| Casing | polycarbonate, white |
| Ex-rating | EX II 1G EEx ia IIC T5 (at max. 40 °C) |
| Average quiescent current | 85 µA at 24 VDC |
| Starting current | 105 µA at 24 VDC |
| Alarm load | 325 Ω in series with 1.0 V voltage drop |
| Operating temperature | -40 °C to +60 °C (class T4) -40 °C to +40 °C (class T5) (Protect against condensation and icing!) |
| Heat detector | rate-of-rise detector |
| Response grade according to EN 54-5:2000 | AR1, max. room temperature 50 °C |
| Alarm indicator | red luminous diode on the detector |
Sản phẩm khác
Point level switch Soliswitch FTE20 Rotary paddle switch Code: FTE20-AA16AA42 Endress Hauser Vietnam
Giá: Liên hệ
Proline Promag P 200 Electromagnetic flowmeter Code: 5P2B1F-AAACCAED3K1A+AKZ1 Endress Hauser Vietnam
Giá: Liên hệ
Absolute and gauge pressure Cerabar Code: PMC51-AA21JD1PGBRLCA+N8PA Endress Hauser Vietnam
Giá: Liên hệ
Proline Promag P 300 Electromagnetic flowmeter 5P3B15-AAIBAEAFAAED5K2AA1+LA Endress Hauser Vietnam
Giá: Liên hệ





E-mail: sale09@ltdautomation.com.vn